Through simulations and field experiment on A.C. parallel operation of both Utility Interactive Photovoltaic System and Diesel Engine Revolving Field Type Synchronous Generator, following factors have been found.
First, the inverter should be operated in three modes of frequency(mode.1: ±0.3 ㎐ mode.2: ±l ㎐ mode.3: ±2 ㎐ as default, considering properties of operating Synchronous Generator.
Second, as a result of supplying 13.5 ㎾ of residual power, it has been found that Synchronous Generator takes the power input only as reactive power, because it was electrically stable with frequency of 60.14㎐ and high voltage of 222.3V even when power factor was -0.94. Besides, it was mechanically stable, too, because the quake, noise, and temperature of Synchronous Generator in this case were 7.5 ㎜/s, 97 ㏈ and 6 ℃ respectively, which were lower than normal load connection of 145.6 ㎾ 11.03 ㎜/s. Thus, load share of Revolving Field Type Synchronous Generator reduces according to the supply of Photovoltaic System to the load power. In this experiment, 200㎾ of Synchronous Generator and 40 ㎾ of Photovoltaic System were operated in parallel. The load share was 20% in maximum, and 11.1lit/hr of fuel was saved.

목차

Abstract
1. 서론
2. 재료 빛 방법
3. 결과 및 고찰
3. 요약 및 결론
참고문헌

참고문헌 (0)

참고문헌 신청

함께 읽어보면 좋을 논문

논문 유사도에 따라 DBpia 가 추천하는 논문입니다. 함께 보면 좋을 연관 논문을 확인해보세요!

이 논문의 저자 정보

이 논문과 함께 이용한 논문

최근 본 자료

전체보기

댓글(0)

0

UCI(KEPA) : I410-ECN-0101-2010-563-001428178